®Environmental Monitoring UnitManagement PeripheralAP9312THAP9312THiInstallation and Quick Start Manual
6Installation, continuedConnection process: overviewYou must perform two procedures to set up contact monitoring.• See “Contact Sensors” on page 7 to
7Contact SensorsSelecting sensorsTo monitor circuits that have no voltage potential of their own, you can use any normally open (NO) or normally close
8Contact Sensors, continuedSensor zone descriptionThe following figure shows the screw terminal connector and the connector pins with their associated
9Contact Sensors, continuedConnection informationThe Environmental Monitoring Unit supports normally open and normally closed loop systems and allows
10Contact Sensors, continuedExample of a typical hookupIn this example: •Zone 1 is a normally-closed zone with power for the passive infrared detector
11Quick ConfigurationRequired and optional settingsYou must configure the following network settings of the Environmental Monitoring Unit before it ca
12Quick Configuration, continuedConfiguring TCP/IP settings, continuedSerially through the Control Console. If you are not using a Windows-based platf
13Quick Configuration, continuedConfiguring TCP/IP settings, continuedOver the Network by ARP. To configure the Environmental Monitoring Unit’s TCP/IP
14Quick Configuration, continuedAccessing the unitYou can access the Environmental Monitoring Unit by using a Web browser, Telnet, or SNMP. Through a
15Warranty InformationLimited warrantyAmerican Power Conversion (APC) warrants the Environmental Monitoring Unit to be free from defects in materials
This manual is available in English on the enclosed CD.❖❖❖Dieses Handbuch ist in Deutsch auf der beiliegenden CD-ROM verfügbar.❖❖❖Este manual está dis
16TroubleshootingMaintenanceThe Environmental Monitoring Unit requires periodic maintenance. • To remove any visible buildup of dust from the temperat
17Troubleshooting, continuedIf problems persistIf a problem is not mentioned in “Correcting problems” on page 16, or if the problem persists:1. Note t
18SpecificationsElectrical specificationsPhysical specificationsContinued on next pageItem SpecificationInput voltage, nominal24 VDCMaximum total curr
19Specifications, continuedEnvironmental specificationsApprovalsRadio Frequency InterferenceThis equipment has been tested and found to comply with th
20Life-Support PolicyGeneral policyAs a general policy, American Power Conversion (APC) does not recommend the use of any of its products in the follo
Declaration of ConformityApplication of Council Directives89/336/EECStandards to Which Conformity isDeclaredEN55022, EN55024Manufacturer’s Name and Ad
APC Worldwide Customer SupportCustomer support for this or any other APC product is available at no charge in any of the following ways:• Visit the AP
iContentsIntroduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Features 1Product inventory 2Additional probes 3Please recycl
iiContents continuedTroubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . 16Maintenance 16Correcting problems 16If problems persist
1IntroductionFeaturesAmerican Power Conversion’s stand-alone Environmental Monitoring Unit (AP9312TH and AP9312THi) continuously senses temperature an
2Introduction, continuedProduct inventoryContinued on next page!Rack-mount brackets with 4 flat-head screws (870-8213A and 870-8183)"AC power ada
3Introduction, continuedAdditional probesTo order a second temperature and humidity probe (AP9512TH), call APC Customer Support at a number listed on
4InstallationInstalling outside an enclosureTo install the Environmental Monitoring Unit outside an enclosure, place it on a flat surface in a protect
5Installation, continuedInstalling in an enclosure, continued4. Attach the assembly tightly to the enclosure using four mounting screws and four plast