American Power Conversion AP7601 User Manual Page 11

  • Download
  • Add to my manuals
  • Print
  • Page
    / 24
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 10
Three-Phase Rack PDU Installation and Operation Manual 7
Configuration
How to configure the
PDU through a serial
port
1. Connect an available serial port on your computer to the serial port
on the Rack PDU, using the supplied configuration cable
(990-0144). The PDU’s serial port is shown below.
2. Run a terminal emulation program such as Windows
®
HyperTerminal.
3. Configure the following settings for the serial port:
19,200 bps
–no parity
–8 data bits
–1 stop bit
no flow control
4. Press any key on the computer to display the PDU login screen,
which contains the Username and Password prompts.
5. Log on by using the user name and password for the appropriate
access level:
Note
If you have InfraStruXure Manager as part of your system,
you can use InfraStruXure Managers Web interface to
configure the same values that are configured through a
serial port.
Note
Some terminal emulation programs require that a
device be disconnected and then reconnected for the
new serial port settings to take effect.
Access Level
Default User
Name
Default Password
Administrator Press ENTER.Type apc (lowercase).
User Press
ENTER.Press ESC.
Page view 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 23 24

Comments to this Manuals

No comments