990-7031C, Revision 4 12/99APC Smart-UPSUninterruptible Power SupplyModels1400XLT, 2200XLT, 3000T, 5000TUser’s Manual
990-7031C, Revision 4 12/9943 Expand the rails so that it spans from the front rack post tothe back rack post. Replace the two screws (remov
990-7031C, Revision 4 12/9952. Connect the BatteriesNote:All UPSs ship with the batteries disconnected. In addition, 5000 VA units have the batterie
990-7031C, Revision 4 12/9963U Rack Mount Units 1. Reach into the finger pull and open the front cover. Swing the cover open as shown. 2. Unhook
990-7031C, Revision 4 12/9973. Connect Power and Equipment to the UPS• Connect the UPS line cord (L6-30 plug) into the electrical outlet.• Use your
990-7031C, Revision 4 12/998Charge the batteryThe UPS charges its battery whenever it is connected to utility power. The battery will charge fully dur
990-7031C, Revision 4 12/999Operating InstructionsSwitch On — Switch Off With the UPS plugged in, press and release the large upper on/test button to
990-7031C, Revision 4 12/9910Load Bar Graph85%67%50%33%17%The 5-LED display on the left of the front panel represents the power drawn from the UPS as
990-7031C, Revision 4 12/9911StorageStorage ConditionsStore the UPS covered and upright in a cool, dry location, with its battery fully charged. Befo
990-7031C, Revision 4 12/9912Battery Replacement Procedure - Tower Units5000 VA1. Grasp the top edge of the bottom front cover and tilt it out.For th
990-7031C, Revision 4 12/9913Battery Replacement Procedure - 3U Rack Mount Units 1. Reach into the finger pull and open the front cover. Swing the
Entire contents copyright ©1999 by American Power Conversion. All rights reserved. Reproduction in whole or in part withoutpermission is prohibited.
990-7031C, Revision 4 12/9914Battery Replacement Procedure - 5U Rack Mount Units5000 VA1. Reach into the finger pull and open the front cover. Swing
990-7031C, Revision 4 12/9915User Configuration ItemsNote: Setting these items requires optional software or hardware.Function Factory Default User Se
990-7031C, Revision 4 12/9916Tower and 5U Rack Mount Models - 3000 & 5000 VA ModelsTypical On-Battery Run Time Versus Load, in HoursLoad 3000 VA I
990-7031C, Revision 4 12/9917Specifications1400 VA 2200 VA 3000 VA 5000 VAAcceptable input voltage 0 - 325 VACInput voltage (on-line operation)* 160 -
990-7031C, Revision 4 12/9918TroubleshootingUse the chart below to solve minor UPS installation problems. Contact APC Technical Support Staff for ass
990-7031C, Revision 4 12/9919ServiceIf the UPS requires service do not return it to the dealer!Follow these steps:1. Review the problems discussed in
990-7031C, Revision 4 12/9920Appendix A: XL InformationWhen used with external battery packs, the extended run (XL) UPS offers longer run times than
990-7031C, Revision 4 12/9921Smart-UPS Battery ProtocolSmart-UPS XL models are not designed to know how many external battery packs are connected to t
990-7031C, Revision 4 12/9922Use the HyperTerminal Program to Change the Number of External Battery PacksHyperTerminal is used for Windows 95, Windows
990-7031C, Revision 4 12/9923Appendix B: Types of Racks and Mounting HardwareThis appendix describes the hardware required for the different types of
990-7031C, Revision 4 12/99Smart UPS Safety Guide EnglishThis Safety Guide contains important instructions that should be followed during installation
990-7031C, Revision 4 12/9924Appendix C: Transporting Your Smart-UPSFollow these guidelines if you need to ship the UPS to another location. These g
990-7031C, Revision 4 12/99Table of ContentsIntroduction...
990-7031C, Revision 4 12/991IntroductionThis Uninterruptible Power Supply (UPS) is designed to prevent blackouts, brownouts, sags and surges from reac
990-7031C, Revision 4 12/992InstallationInstalling your UPS requires five steps:1. Position the UPS in the desired location. For rack mount units th
990-7031C, Revision 4 12/993Determine the Location of the UPS in the RackUPSs are heavy. Select a rack location sturdy enough to handle the weight.