DC Power Plant Product Manual MX28B600 December 2002 APC DCNS Inc. 11035 Switzer Avenue Part# 990-0564 Dallas, TX 75238
MX28B600 - 6 - 4. PRODUCT OVERVIEW AND TECHNICAL DESCRIPTION 4.1 Description The MX28B600 is a modular stand-alone -48V DC power plant with a micro
MX28B600-48V 7 Figure 4.1-2. MX28B600 BLOCK DIAGRAM
MX28B600-48V 8 4.2 Power Output Capacity 600 amps maximum, or 550 amps with N+1 redundancy. The housing provides space for three rectifier shelves t
MX28B600-48V 9 4.5 AC Input Power Each rectifier requires 208/220/240V AC, single-phase, 50/60 Hz, supplied through an external 20-amp two-pole breake
MX28B600-48V 10 4.7 DC Distribution Two plug-in circuit breaker tiers, consisting of a 24-position panel and two 10-position panels, provide 43 positi
MX28B600-48V 11 4.10 Mechanical • Dimensions: 42" high x 23" wide x 20"deep (1066x584x508mm) • Weight: Housing - 190 lbs. (86kg
MX28B600-48V 12 5. INSTALLATION PROCEDURES 5.1 Preparation 5.1.1 Recommended Tools • Standard selection of insulated hand tools. • Proper tools for
MX28B600-48V 13 Prior to installation, drawings, floor loading requirements, external alarm points, AC service entrance, and grounding schemes should
MX28B600-48V 14 5.3.1 Cable Sizing Considerations The battery cable(s) should be sized sufficiently large to limit the voltage drop from the MX28B600
MX28B600-48V 15 Figure 5.6 Interface Board 5.6.1 External Alarm Inputs Four external alarm inputs with assignable priority levels are available.
REVISION HISTORY Revision Date By Description 07/10/01 JNF Initial release. 10/30/02 BET Changed breaker numbering
MX28B600-48V 16 5.6.2 Alarm Outputs There are eight alarms available that provide outputs via Form “C” relay contacts. The last two of these are pre-
MX28B600-48V 17 BREAKER RATING PART NUMBER BREAKER RATING PART NUMBER 1 A FFA-0014 40 A FFA-0020 3 A FFA-0015 50 A FFA-0025 5 A FFA-001
MX28B600-48V 18 5.7.2 Installation of Circuit Breakers and Fuses 5.7.2.1 Plug-in Circuit Breakers 1) Remove the circuit breaker cover panel and the
MX28B600-48V 19 J5a 50 A. circuit breaker located in circuit breaker Position 1. The interface card provides fuseholders for eight fuses, labeled “F1
MX28B600-48V 20 5.9.1 Apply AC Power Turn on the circuit breakers that supply AC power to the rectifiers in the MX28B600 DC power plant. The main s
MX28B600-48V 21 3) Turn on all the circuit breakers that supply AC power to the rectifiers in the MX28B600 DC power plant. 4) Load circuit breakers
MX28B600-48V 22 6. SETUP, ADJUSTMENTS, AND OPERATION 6.1 User Interface The MX28B600 control unit provides a user interface designed with a hierarch
MX28B600-48V 23 6.3 External Alarm Inputs The four external alarm inputs (also referred to as “Input Relay Alarms”) can be assigned a priority and ro
MX28B600-48V 24 Table 6.5-1. Parameter Locations, Descriptions, and Default Values PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGSSYSTEM S
MX28B600-48V 25 (Table 6.5-1. Parameter Locations, Descriptions, and Default Values) PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS Disp
TABLE OF CONTENTS 1. GENERAL INFORMATION...1 1.1 INTROD
MX28B600-48V 26 (Table 6.5-1. Parameter Locations, Descriptions, and Default Values) PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS Te
MX28B600-48V 27 (Table 6.5-1. Parameter Locations, Descriptions, and Default Values) PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS Batte
MX28B600-48V 28 (Table 6.5-1. Parameter Locations, Descriptions, and Default Values) PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS Stan
MX28B600-48V 29 (Table 6.5-1. Parameter Locations, Descriptions, and Default Values) PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS FUSE
MX28B600-48V 30 (Table 6.5-1. Parameter Locations, Descriptions, and Default Values) PARAMETER DESCRIPTION DISPLAY SCREENS / DEFAULT SETTINGS Ou
MX28B600-48V 31
MX28B600-48V 32 Figure 6.4-1. Control Unit Menu Structure MX28B600 + STATUS Sys Voltage Sys Current Sys Temp B
MX28B600-48V 33 (Figure 6.4-1. Control Unit Menu Structure) Address 2 Address 3 Model Fahrenheit
MX28B600-48V 34 (Figure 6.4-1. Control Unit Menu Structure) Test Relay En Test Relay 1 Test Relay 2
MX28B600-48V 35 Cir Bkr 7 Cir Bkr 8 • • •
MX28B600 - ii - 5.7.2 Installation of Circuit Breakers and Fuses...18
MX28B600-48V 36 (Figure 6.4-1. Control Unit Menu Structure) LVD SET-ALM LVD1 Option LVD1 Open Al
MX28B600 - 1 - 1. GENERAL INFORMATION 1.1 Introduction DC Power Plants from APC DC Network Solutions Inc. (hereafter in this document “APC”) have u
MX28B600 - 2 - 1) Make a descriptive notation on the delivery receipt before signing. 2) File a damage or shortage report with the carrier that d
MX28B600 - 3 - 2. CUSTOMER SERVICE AND SUPPORT APC manufactures standby power plants and systems, and provides customers with complete product an
MX28B600 - 4 - 3. WARRANTY PROVISIONS 3.1 General Provisions APC DC Network Solutions Inc. warrants the power equipment and components it manufactu
MX28B600 - 5 - 5. APC shall not be liable to the user (purchaser), or any third party, for indirect, incidental, or consequential damages such as,