MasterSwitch VM Users Guide 15
Menu Items
Outlets continued
Synchronized set
configuration
Outlets that are members of a synchronization set will all execute the
same control action simultaneously (within
16
milliseconds). In a
configuration where multiple redundant power cords are being used in a
daisy-chain configuration, this feature permits synchronized switching
across units.
When you configure a synchronization set, you can assign an outlet to
only one set, and all the outlets in a specified set assume the
characteristics of the lowest numbered outlet. If you make changes to
any of the outlets in a given set, all of the outlets will take on the new
characteristics.
Note: In the Outlets menu, you can identify the synchronization set to
which an outlet belongs by the number in brackets. For
example:
(unit #: outlet # [synchronization set #])
Item Definition
Set Number Identifies a specific set of outlets.
Member Outlets Identifies the outlets assigned to a given set.